Product Overview
The intelligent wireless automatic gas fire extinguishing host includes a CPU main control unit, an alarm unit, a communication unit, and a display unit. By connecting with the wireless gas fire extinguishing device on site, it can accurately receive the environmental data transmitted by the fire extinguishing device. Through calculation and analysis, it can determine whether it exceeds the standard. If it exceeds the standard, it will give an audible and visual alarm. The intelligent wireless automatic gas fire extinguishing host adopts a 10 inch LCD touch screen, which is used to display real-time data measured on site, perform historical data query, system time setting, alarm parameter setting and other operations. The operation interface is simple and friendly, and adopts wall mounted installation method.
Function and Features
◇ Digital processing technology, real-time monitoring and display of the environmental status of each distribution cabinet
◇ RS485 communication technology, real-time and accurate transmission of operating parameters and control instructions
◇ LORA, 4G wireless communication technology ◇ High risk warning alarm
◇ Data intelligent analysis, intelligent parameter setting ◇ Remote start intelligent fire extinguishing device ◇ System self check, network inspection function
◇ Sound and light alarm function
◇ Alarm, fault record storage, and query function technical indicators

Host installation wiring
◇The installation distance between the host and the fire extinguishing device should be kept within 200m as much as possible.
◇ The host adopts wall mounted installation.
◇ The host should be connected to a configured 4G or LORA antenna according to the needs of the scenario.
◇ The host is connected to an external AC220V power supply.
Installation and wiring of fire extinguishing devices
◇The fire extinguishing device is generally installed on the lower side of the inner surface of the distribution box cabinet.
◇ The fire extinguishing device is installed using magnetic suction or screw fixation.
◇ The fire extinguishing device takes AC220V power from the cabinet through a power adapter (standard).
◇ The temperature sensing cable is used for temperature measurement throughout the entire section, and is routed in a serpentine manner inside the distribution box cabinet (Figure 2). When an open flame occurs at any position, it can trigger automatic fire extinguishing as soon as possible.
◇ The two-stage combination product design allows users to easily replace the fire extinguishing compartment after using the fire extinguishing device, reducing usage costs through repeated use.